Exciter Model: ST1C

 

Model Equations and/or Block Diagrams

Parameters:

OEL OEL input: if < 2, add to error signal; if = 2, LV gate 1; if = 3, LV gate 2
UEL UEL input: if < 2, add to error signal; if = 2, HV gate 1; if = 3, HV gate 2
VOS PSS input: if = 1, add to error signal; if = 2, add after HV gate 1
Tr Filter time constant, sec
ViMax Maximum error, pu
ViMin Minimum error, pu
Tc Lag time constant, sec
Tb Lead time constant, sec
Tc1 Lag time constant, sec
Tb1 Lead time constant, sec
Ka Gain, pu
Ta Voltage regulator time constant, sec
VaMax Maximum control element output, pu
VaMin Minimum control element output, pu
Vrmax Maximum control element output, pu
Vrmin Minimum control element output, pu
Kc Rectifier regulation factor, pu
Kf Rate feedback gain, pu
Tf Rate feedback constant, sec
Klr Gain on field current limit
Ilr Maximum field current, pu